Tuesday, April 19, 2011

Ampacity Calc: 10 AWG: 35.0A


Wiring/Table: Conductors (310.16/18)
Temp/Conductors: 75c Copper

Types:RHW, THHW, THW, THWN, XHHW, USE, ZW

Wire Size: 10 AWG
Base Ampacity: 35.0A

# Current Carrying Conductors: 1-3

Ambient Temperature: 26-30c, 78-86F

RESULT: 35.0 Amperes
Be Aware of 240.4(D) OCPD Limitations

Ampacity: 35 Amperes
Continuous: 28.0 Amperes
Be Aware of 240.4(D) OCPD Limitations